How to add r-410 Refrigerant

How to Add R-410 Refrigerant

By Robert Sylvus

An azeotrope refrigerant blends multiple refrigerant compounds to form a single refrigerant. Most refrigerant blends boil at different rates and require complete evacuation before adding a full charge. This is not the case with so R-410, which is considered a near-azeotrope, using compounds that boil at almost the same rate. Manufacturers include a refrigerant charge in new air conditioning systems that will provide the correct amount of refrigerant for the unit and a 15 to 25 foot refrigerant line set. Long line sets, the copper lines that the refrigerant travels through, will require additional R-410 refrigerant.

...
R-410 refrigerant operates at a higher pressure than R-22.
Step 1

Turn the air conditioning system off at the thermostat.

Step 2

Check the identification tag on the outdoor condensing unit to verify the system uses R-410 as a refrigerant. Mixing R-410 with any other refrigerant will cause the compressor to seize.

Step 3

Connect the middle hose from an R-410 refrigeration manifold gauge set to a jug of R-410 (pink colored). Most hoses use screw-on fittings, but some use low-loss fittings that snap into place.

Step 4

Open the R-410 jug's valve by turning the handle clockwise.

Step 5

Remove the caps from both service valves, found where the refrigerant lines enter the condenser. Use an adjustable wrench to loosen them, if needed. The liquid refrigerant service valve connects to the small copper refrigerant line. The large refrigeration line, called the suction line, holds the vapor refrigerant as it returns to the condenser.

Step 6

Open the manifold's right-hand handle for one second then close the handle. This will purge the air and moisture from the manifold and the high-pressure hose. The handle opens when turned clockwise.

Step 7

Connect the hose on the manifold's right-hand side, high-pressure side, to the liquid refrigerant's service valve port. Screw-on fittings will screw onto the port, whereas low-loss fittings will snap into place.

Step 8

Purge the low-pressure, left-hand side hose for one second.

Step 9

Connect the manifold's low-pressure hose, left-hand side, to the suction-line service valve's port. Screw-on fittings will screw onto the port, and low-loss fittings will snap into place.

Step 10

Turn the air conditioner on at the thermostat. Allow the system to run for 10 minutes.

Step 11

Measure the temperature of the liquid refrigerant line 6 inches from the service valve with a thermometer. Write down this measurement.

Step 12

Check the high-pressure gauge, right-hand side, on the R-410 manifold set. The gauge will have a pressure reading in pounds per square inch gauge (PSIG) and a R-410 refrigerant saturation temperature measured in degrees Fahrenheit (F).

Step 13

Subtract the PSIG reading from the F reading. The resulting number will equal the subcooling value.

Step 14

Check the condenser's label for the designed subcooling value. If the calculated subcooling value reads less than the stated subcooling valve, then add R-410 to the system. Do not overcharge the system. Technicians often allow +/- 3 degrees for measurement error.

Step 15

Flip the R-410 refrigerant jug over. Always charge R-410, as a liquid, with the valve and hose facing the ground. Vapor charging will separate the refrigerant blend.

Step 16

Throttle the low-pressure, left-hand side manifold valve for 60 seconds. Throttling, i.e., opening and closing the valve every five seconds, will deliver a fully mixed refrigerant blend in liquid form without flooding the compressor.

Step 17

Allow the system pressures to equalize. When the gauge's needles have stopped dropping, the system pressures have equalized. This can take up to two minutes.

Step 18

Calculate the new subcooling value and compare it to the designed subcooling value as stated on the condenser's label. Add R-410 refrigerant as needed.

Step 19

Close the manifold and R-410 jug's valve handles. Disconnect the hoses and reinstall the caps on the service valve's ports.

댓글

이 블로그의 인기 게시물

Kavo VS. MDK

-  행적 : 12시 30분 점심 먹고 집 출발 => 사무실 들러 핸드피스 같은 것 챙겨서 => 뉴욕으로 출발 => 하바디언 들려 임프레션, 힐링 배달하고 => DC 들려 Air motor 교체 해주고 => 홍치과 들려 센서 교체해주고 => 뉴저지로 돌아와 나이스 덴탈랩 배달하고 => 하나치과 들려 정리 방안 확정하고 집으로 돌아옴

회사 사보 창간호에 보내준 글

제 인생의 Turning Point 돌이켜 생각해보면 나름대로 재미 있는 인생이었는지 몇몇 장면들에서 입가에 웃음이 절로 번지집니다. 물론 지금까지도 '아~ 그것만은 하지 말았어야 했는데.. ' 라고 혼자말이 나오는 순간도 있 습니다. 그 몇 장면중에서 제가 힘들고 상심했었을 때 중탕 흑염소가 되었던 말 한마디를 소개할까 합니다.  군대를 다녀와서 남은 대학 1년을 어떻게 보낼 것인가를 놓고 생각해봤습니다. 궁리 끝에 몇가지 목표를 정하게 됐는데 첫째는 어머님이 그토록 바라시던 장학금을 타는 것이고 둘째는 창작 시나리오를 한 편 쓰는 것이었고 마지막 하나는 청춘이 다 가기전에 그럴 듯한 '사랑'을 한번 해보는 것이었습니다. 첫째, 둘째는 노력(=군인정신?)과 더불어 찾아온 행운으로 달성하게 되었지만 역시 세번째가 꽤 복잡 미묘하고 어려운 미해결 문제였습니다. 삼형제 집안에서 자란 탓에 터프, 단순, 뒷끝 없음을 생활 신조로 자란 지라 연애를 함에 있어 꼭 필요해 보이는 드라마틱한 접근, 주기적 이고  감동적 인 이벤트 준비, 다소 시시콜콜한 이야기를 인내심을 가지고 들어주기 등의 필수 교양이 명백히 부족했 었지요 . 지하철에서 본 어떤 멋진 숙녀분을 용감하게 쫗아가서 연락처를 드린 적이 있습니다. 글쎄 시도는 좋았다고 지금도 생각되는데 마무리가 좀 그랬습니다. 연락처를 드리면서 " 제가 지금 선배님 결혼식에 가야되서 더 이상 쫓아 갈 수가 없습니다. 그리니 이 연락처로 이번 주 중에 전화를 주시면 좋겠습니다. 꼭이요~" 당연히 전화는 안왔고 아무 일도 생기지 않았습니다. 여자 동기, 후배들 목록, 기타 인연이 될만한 목록을 점검해 보며 몇 번 더 몸부림을 쳐봤지만 그저 혼자 떨 뿐 공명은 없었습니다. 그러던 중에 겨울이 찾아오고 어김없이 첫눈이 왔지요. 창밖에 포근하게 내리는 첫눈을 보면서.. 보면서.. 조금씩 위축되어 가 는 저를 느 끼던 그 순간.. 전화벨이 울렸습니다. ...